feat(understand): cable_takeoff - one row per load, rounded to the metre

cable_rows reads each load's power, phases, voltage, neutral and VFD from the
P&ID's electrical texts near its tag, and its panel from the layout's wiring
callouts (else the P&ID's), names normalised CP 1 -> CP-1. The length is the
Manhattan distance on the layout from the tag to its panel, and the cable
ROUNDUP(length x (1 + allowance)) to the metre, on the length rounded to
1e-6 m so binary noise never buys a metre. Power is never invented: a load
with no stated kW keeps an empty cell and an open item. Without a layout the
lengths stay empty with an open item per row. Room and panel totals count a
panel package's power once, never its children's as well; the rule is on the
method sheet. Sections only from the caller's section_rules - no standard
table exists here.

The workbook gains the cable shape (Metraj, Ozet by room and panel, Kontrol
as the open-items list, Metodoloji) in the same three languages;
cable_takeoff joins SECTION 27. Inventory regenerated; README snapshot 243
tools (238 advertised); registry snapshot analysis: 14.

Co-Authored-By: Claude Opus 5.5 (1M context) <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01FKFStjEFzpGyLq5bMpWxTd
This commit is contained in:
Umut CAN
2026-09-24 12:28:59 +03:00
co-authored by Claude Opus 5.5
parent 653535bcc1
commit 459d3b9228
10 changed files with 1110 additions and 15 deletions
+106 -1
View File
@@ -10555,7 +10555,7 @@ async def arch_plan_from_spec(
# ---------------------------------------------------------------------------
# ── SECTION 27: Plant Takeoffs (1 tool) ─────────────────────────────────────
# ── SECTION 27: Plant Takeoffs (2 tools) ────────────────────────────────────
# ---------------------------------------------------------------------------
@@ -10714,6 +10714,111 @@ async def pipe_takeoff(
raise ToolError(str(exc)) from exc
@cad_tool(
summary="Cable takeoff: one row per load, Manhattan length to its panel, rounded up to the metre.",
cost="safe",
)
@mcp.tool(
annotations={
"title": "Plant: Cable Takeoff",
"readOnlyHint": False,
"destructiveHint": False,
},
tags={"plant", "analysis"},
)
async def cable_takeoff(
pid_path: Annotated[
str | None,
Field(
default=None,
description="The P&ID carrying the electrical texts (kW, phases, voltage, VFD). "
"Omit to read the current drawing.",
),
] = None,
layout_path: Annotated[
str | None,
Field(
default=None,
description="The layout with the tags, the panels and the 'Wiring to CPn' "
"callouts. Omitted, every length stays empty with an open item.",
),
] = None,
output: Annotated[
str | None,
Field(
default=None,
description="Workbook to write (.xlsx); the four sheets are also written as CSV "
"beside it. Omit to return the rows only.",
),
] = None,
lang: Annotated[
str, Field(default="en", description="Headers and method text: tr | en | ru.")
] = "en",
allowance: Annotated[
float,
Field(
default=0.20,
ge=0.0,
le=1.0,
description="Allowance before rounding up to the metre (0.20 = 20 %).",
),
] = 0.20,
section_rules: Annotated[
list[dict] | None,
Field(
default=None,
description="Your own section table: [{max_kw, section, phases (1|3, optional)}], "
"e.g. [{'max_kw': 5.5, 'section': '5x2.5'}]. Omitted, no section is proposed.",
),
] = None,
ctx: Context = None,
) -> dict:
"""A cable takeoff: one row per electrical load, the shop's cable method made repeatable.
Power, phases, voltage, neutral and VFD come from the P&ID's electrical
texts near each tag (Russian, Turkish and English spellings). **Power is
never invented**: a load with no stated kW keeps an empty cell and an open
item. The panel comes from the layout's wiring callouts ('Wiring to CP1'
and its variants, normalised to CP-1), else from the P&ID. The length is the
Manhattan distance on the layout from the load's tag to its panel's tag,
and the cable is ROUNDUP(length x (1 + allowance)) to the metre. Room and
panel totals count known power once: a load wired to a panel that states
its own power is part of that package, and the package's power is counted
instead of its children's - the rule is written on the method sheet.
Sections only from `section_rules`; no standard table is applied. Open
items: missing power, missing panel, a tag or panel not on the layout, no
layout at all, a load no section rule covers.
Read-only on both drawings. With `output` it writes one workbook - Metraj,
Özet, Kontrol, Metodoloji - as XLSX and, always, as CSV beside it.
Refused before a drawing is read: `lang` outside tr / en / ru, an allowance
outside 0-1 and a malformed section rule (named by its path,
`section_rules[0].section: ...`). A missing, unreadable or oversize drawing
is refused by the reader, which names MAX_DXF_BYTES. Without openpyxl the
XLSX is not written and `files.refused` carries `capability: "xlsx_write"`
naming the `office` extra; the CSV files are written all the same.
"""
from engineering.understand.draw import run_cable_takeoff
pid = str(validate_path(pid_path)) if pid_path else None
layout = str(validate_path(layout_path)) if layout_path else None
target = str(validate_path(output, allow_write=True)) if output else None
await ctx.info(f"cable_takeoff: {pid or 'current drawing'} / {layout or 'no layout'}")
try:
return await run_cable_takeoff(
_backend(ctx),
pid_path=pid,
layout_path=layout,
output=target,
lang=lang,
allowance=allowance,
section_rules=section_rules,
)
except (ValueError, OSError) as exc:
raise ToolError(str(exc)) from exc
# ---------------------------------------------------------------------------